XLPE Insulated, PVC Sheathed 2 core+E Armored Cables, 0.6/1kV

Application

These cables are used for mains, submains and subcircuits unenclosed, enclosed in conduit, buried direct or in underground ducts for buildings and industrial plants where not subject to mechanical damage.

Standard

  • AS/NZS 5000.1
  • AS/NZS 3008
  • AS/NZS 1125

Cable Construction

CONDUCTOR Plain annealed copper.
INSULATION XLPE X-90.
INSULATION COLOUR: 2C + E - Red, Black, Green/yellow
BEDDING: Polyvinylchloride compound PVC 5V-90
BEDDING COLOUR: Black
ARMOUR: Galvanised Steel Wire
SHEATH: Polyvinylchloride compound PVC 5V-90
SHEATH COLOUR: Orange, other colors are available upon request

Technical Characteristics

XLPE Insulated, PVC Sheathed 2 core+E Armored Cables

CONDUCTOR CURRENT RATINGS ELECTRICAL CHARACTERISTICS
NOMINAL AREA MM2 UNENCLOSED IN AIR
A
BURIED DIRECT A BURIED IN DUCTS A MAXIMUM
DC
RESISTANCE
@20°C
OHM/KM
MAXIMUM AC RESISTANCE
@90°C
OHM/KM
REACTANCE OHM/KM SINGLE PHASE VOLTAGE DROP
@90°C
MV/AM
16 97 130 100 1.15 1.47 0.0805 2.95
25 130 170 130 0.727 0.927 0.0808 1.86
35 160 205 160 0.524 0.669 0.0786 1.35
50 195 245 190 0.387 0.494 0.0751 1.00
70 250 300 235 0.268 0.343 0.0741 0.703
95 310 360 285 0.193 0.248 0.0725 0.520
120 360 410 325 0.153 0.197 0.0713 0.423

Cable Parameter

NOM. CONDUCTOR AREA
MM2
CONDUCTOR NO./ OD NOM. INSULATION THICKNESS MM NOM. EARTH CONDUCTOR AREA
MM2
NOM. EARTH
CONDUCTOR INSULATION THICKNESS MM
NOM.
DIAMETER OVER BEDDING MM
ARMOUR DIAMETER MM NOM. OVERALL DIAMETER MM APPROX. MASS KG/KM
16 7/1.70 0.7 6 0.7 15.3 1.25 21.6 1100
25 7/2.14 0.9 6 0.7 19.2 1.25 25.8 1310
35 7/2.65 0.9 10 0.7 21.3 1.6 26.8 1765
50 19/1.89 1.0 16 0.7 24.1 1.6 29.7 2185
70 19/2.24 1.1 25 0.9 28.2 1.6 33.6 2745
95 19/2.65 1.1 25 0.9 31.7 2.0 37.7 3650
120 19/2.94 1.2 35 0.9 35.4 2.0 41.8 4600